V
0
, the thermal measured value of overload protection Θ/Θ
off
, the real power P, reactive power Q, and appa-
rent power S, the frequency; and the power factor cos
ϕ
are calculated as primary values (including the date
and time they were last updated).
The minimum and maximum values of the long-term averages listed in the previous section are also calcu-
lated.
The minimum and maximum values can be reset at any time via binary inputs or by using the integrated
control panel or the DIGSI software. Additionally, the reset can be carried out cyclically, starting at a preset
point of time.
Setting Notes
Minimum and Maximum Values
The tracking of minimum and maximum values can be reset automatically at a programmable point in time.
To select this feature, address 8311
MinMax cycRESET
should be set to
YES
. The point in time when reset is
to take place (the minute of the day in which reset will take place) is set at address 8312
MiMa RESET TIME
.
The reset cycle in days is entered at address 8313
MiMa RESETCYCLE
, and the beginning date of the cyclical
process, from the time of the setting procedure (in days), is entered at address 8314
MinMaxRES.START
.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
8311
MinMax cycRESET
NO
YES
YES
Automatic Cyclic Reset Function
8312
MiMa RESET TIME
0 .. 1439 min
0 min
MinMax Reset Timer
8313
MiMa RESETCYCLE
1 .. 365 Days
7 Days
MinMax Reset Cycle Period
8314
MinMaxRES.START
1 .. 365 Days
1 Days
MinMax Start Reset Cycle in
Information List
No.
Information
Type of
Informa-
tion
Comments
-
ResMinMax
IntSP_Ev
Reset Minimum and Maximum counter
395
>I MinMax Reset
SP
>I MIN/MAX Buffer Reset
396
>I1 MiMaReset
SP
>I1 MIN/MAX Buffer Reset
397
>V MiMaReset
SP
>V MIN/MAX Buffer Reset
398
>VphphMiMaRes
SP
>Vphph MIN/MAX Buffer Reset
399
>V1 MiMa Reset
SP
>V1 MIN/MAX Buffer Reset
400
>P MiMa Reset
SP
>P MIN/MAX Buffer Reset
401
>S MiMa Reset
SP
>S MIN/MAX Buffer Reset
402
>Q MiMa Reset
SP
>Q MIN/MAX Buffer Reset
403
>Idmd MiMaReset
SP
>Idmd MIN/MAX Buffer Reset
404
>Pdmd MiMaReset
SP
>Pdmd MIN/MAX Buffer Reset
405
>Qdmd MiMaReset
SP
>Qdmd MIN/MAX Buffer Reset
406
>Sdmd MiMaReset
SP
>Sdmd MIN/MAX Buffer Reset
407
>Frq MiMa Reset
SP
>Frq. MIN/MAX Buffer Reset
408
>PF MiMaReset
SP
>Power Factor MIN/MAX Buffer Reset
412
> Θ MiMa Reset
SP
>Theta MIN/MAX Buffer Reset
837
IAdmdMin
MVT
I A Demand Minimum
838
IAdmdMax
MVT
I A Demand Maximum
839
IBdmdMin
MVT
I B Demand Minimum
840
IBdmdMax
MVT
I B Demand Maximum
2.25.5.2
2.25.5.3
2.25.5.4
Functions
2.25 Auxiliary Functions
SIPROTEC 4, 7SJ62/64, Manual
335
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...