Addr.
Parameter
Setting Options
Default Setting
Comments
171
79 Auto Recl.
Disabled
Enabled
Disabled
79 Auto-Reclose Function
172
52 B.WEAR MONIT
Disabled
Ix-Method
2P-Method
I2t-Method
Disabled
52 Breaker Wear Monitoring
180
Fault Locator
Disabled
Enabled
Enabled
Fault Locator
181
L-sections FL
1 Section
2 Sections
3 Sections
1 Section
Line sections for fault locator
182
74 Trip Ct Supv
Disabled
2 Binary Inputs
1 Binary Input
Disabled
74TC Trip Circuit Supervision
190
RTD-BOX INPUT
Disabled
Port C
Disabled
External Temperature Input
191
RTD CONNECTION
6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD simplex
Ext. Temperature Input Connec-
tion Type
-
FLEXIBLE FCT. 1...20
Flexible Function 01
Flexible Function 02
Flexible Function 03
Flexible Function 04
Flexible Function 05
Flexible Function 06
Flexible Function 07
Flexible Function 08
Flexible Function 09
Flexible Function 10
Flexible Function 11
Flexible Function 12
Flexible Function 13
Flexible Function 14
Flexible Function 15
Flexible Function 16
Flexible Function 17
Flexible Function 18
Flexible Function 19
Flexible Function 20
Please select
Flexible Functions 1...20
Device, General Settings
The device requires some general information. This may be, for example, the type of annunciation to be
issued in the event of an occurrence of a power system fault.
2.1.2
Functions
2.1 General
36
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...