cases, even if the ground current of the own line is measured via a separate ground current transformer, enter
the setting
NO
. This setting exclusively affects the function “Current Sum Monitoring” (see Section
2.12.1 Measurement Supervision
).
Current Connection (Power System)
Via parameter 251
CT Connect.
a special connection of the current transformers can be determined.
The standard connection is
A, B, C, (Gnd)
. It may only be changed if the device is set to measure one or
more ground currents via two current inputs. The standard connection applies to all other cases.
The following diagram illustrates a special connection.
[7sj62-64-mess-2erdstroeme-20070301, 1, en_US]
Figure 2-4
Measurement of two ground currents, example
The phase currents
Ι
A
and
Ι
C
must be connected to the first current input (terminals Q1, Q2) and to the third
(terminals Q5, Q6). At the fourth input (terminals Q7, Q8) the ground current
Ι
N
or
Ι
NS
is connected as usual,
in this case the ground current of the line. A second ground current, in this case the transformer neutral point
current, is connected to the second current input
Ι
N2
(terminals Q3, Q4).
The settings
A,G2,C,G; G->B
or
A,G2,C,G; G2->B
must be used here. Both define the connection of a
ground current
Ι
N2
at the second current input (terminals Q3, Q4). The settings only differ in the calculation of
Ι
B
. In case of
A,G2,C,G; G->B
, the phase current
Ι
B
is determined by phase currents
Ι
A
and
Ι
C
as well as the
measured ground current
Ι
N
or
Ι
NS
at the fourth current input. In case of
A,G2,C,G; G2->B
, the phase
Functions
2.1 General
42
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...