Thermal Overload Protection
Setting Ranges / Increments
K-Factor accord. IEC 60255-8
0.10 to 4.00
Increments 0.01
Time Constant τ
th
1.0 min to 999.9 min
Increments 0.1 min
Thermal Alarm Θ
Alarm
/Θ
Trip
50 % to 100 % of the trip excessive
temperature
Increments 1 %
Current Overload
Ι
Alarm
for
Ι
Nom
= 1 A
0.10 A to 4.00 A
Increments 0.01 A
for
Ι
Nom
= 5 A
0.50 A to 20.00 A
Extension kτ Factor when Machine Stopped
1.0 to 10.0 relative to the time
constant for the machine running
Increments 0.1
Emergency Time T
Emergency
10 s to 15000 s
Increments 1 s
Nominal Overtemperature (for
Ι
Nom
)
40 °C to 200 °C
Increments 1 °C
Trip Characteristic
Formula for primary values:
Trip Characteristic curve for
Ι
/ (k
⋅
Ι
Nom
)
≤
8
with
t
Trip time in minutes
τ
th
Heating-up time constant
Ι
n
Actual load current
Ι
pre
Preload current
k
Setting factor per IEC 60255-8
Ι
Nom
Nominal current for the protected object
Dropout Ratios
Θ/Θ
Trip
Θ/Θ
Alarm
Ι
/
Ι
Alarm
Drops out with Θ
Alarm
approx. 0.99
approx. 0.97
Tolerances
Referring to k ·
Ι
Nom
Referring to Trip Time
2 % or 10 mA for
Ι
Nom
= 1 A, or 50 mA für
Ι
Nom
= 5 A,
2 % class according to IEC 60255-8
3 % or 1 s for
Ι
/(k ·
Ι
Nom
) > 1,25;
3 % class according to IEC 60255-8
Influencing Variables Referring to k ·
Ι
Nom
Power supply direct voltage in range 0.8 ≤ V
PS
/V
HN
≤ 1.15
PS
om
1 %
4.16
Technical Data
4.16 Thermal Overload Protection
482
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...