Directional intermittent ground fault protection
Setting Ranges / Increments
Pickup threshold Vgnd> / 3V0>
2.0 V .. 100.0 V
Increments 1 V
Monitoring time after pickup detected
0.04 s ... 10.00 s
Increments 0.01 s
Pulse no. for detecting the interm. E/F
2 ... 50
Increments 1
Dropout ratio
Dropout ratio Vgnd> / 3V0>
0,95 or (pickup value - 0,6 V)
Tolerances
Measurement tolerance Vgnd> / 3V0>
3 % of setting value
Times
1 % of setting value or 10 ms
Influencing Variables
Power supply direct voltage in range 0.8 ≤ V
PS
/V
PSNom
≤ 1.15
<1 %
Temperature in range 23.00 °F (-5 °C) ≤ Θ
amb
≤ 131.00 °F (55 °C)
<0,5 %/ K
4.19
Technical Data
4.19 Directional intermittent ground fault protection
494
SIPROTEC 4, 7SJ62/64, Manual