Addr.
Parameter
C
Setting Options
Default Setting
Comments
6001
S1: RE/RL
-0.33 .. 7.00
1.00
S1: Zero seq. compen-
sating factor RE/RL
6002
S1: XE/XL
-0.33 .. 7.00
1.00
S1: Zero seq. compen-
sating factor XE/XL
6003
S1: x'
1A
0.0050 .. 15.0000 Ω/mi
0.2420 Ω/mi
S1: feeder reactance per
mile: x'
5A
0.0010 .. 3.0000 Ω/mi
0.0484 Ω/mi
6004
S1: x'
1A
0.0050 .. 9.5000 Ω/km
0.1500 Ω/km
S1: feeder reactance per
km: x'
5A
0.0010 .. 1.9000 Ω/km
0.0300 Ω/km
6005
S1: Line angle
10 .. 89 °
85 °
S1: Line angle
6006
S1: line length
0.1 .. 650.0 Miles
62.1 Miles
S1: Line length in miles
6007
S1: Line length
0.1 .. 1000.0 km
100.0 km
S1: Line length in kilometer
6011
S2: RE/RL
-0.33 .. 7.00
1.00
S2: Zero seq. compen-
sating factor RE/RL
6012
S2: XE/XL
-0.33 .. 7.00
1.00
S2: Zero seq. compen-
sating factor XE/XL
6013
S2: x'
1A
0.0050 .. 15.0000 Ω/mi
0.2420 Ω/mi
S2: feeder reactance per
mile: x'
5A
0.0010 .. 3.0000 Ω/mi
0.0484 Ω/mi
6014
S2: x'
1A
0.0050 .. 9.5000 Ω/km
0.1500 Ω/km
S2: feeder reactance per
km: x'
5A
0.0010 .. 1.9000 Ω/km
0.0300 Ω/km
6015
S2: Line angle
10 .. 89 °
85 °
S2: Line angle
6016
S2: line length
0.1 .. 650.0 Miles
62.1 Miles
S2: line length in miles
6017
S2: Line length
0.1 .. 1000.0 km
100.0 km
S2: Line length in kilometer
6021
S3: RE/RL
-0.33 .. 7.00
1.00
S3: Zero seq. compen-
sating factor RE/RL
6022
S3: XE/XL
-0.33 .. 7.00
1.00
S3: Zero seq. compen-
sating factor XE/XL
6023
S3: x'
1A
0.0050 .. 15.0000 Ω/mi
0.2420 Ω/mi
S3: feeder reactance per
mile: x'
5A
0.0010 .. 3.0000 Ω/mi
0.0484 Ω/mi
6024
S3: x'
1A
0.0050 .. 9.5000 Ω/km
0.1500 Ω/km
S3: feeder reactance per
km: x'
5A
0.0010 .. 1.9000 Ω/km
0.0300 Ω/km
6025
S3: Line angle
10 .. 89 °
85 °
S3: Line angle
6026
S3: line length
0.1 .. 650.0 Miles
62.1 Miles
S3: line length in miles
6027
S3: Line length
0.1 .. 1000.0 km
100.0 km
S3: Line length in kilometer
Information List
No.
Information
Type of
Informa-
tion
Comments
126
ProtON/OFF
IntSP
Protection ON/OFF (via system port)
356
>Manual Close
SP
>Manual close signal
501
Relay PICKUP
OUT
Relay PICKUP
511
Relay TRIP
OUT
Relay GENERAL TRIP command
533
Ia =
VI
Primary fault current Ia
534
Ib =
VI
Primary fault current Ib
535
Ic =
VI
Primary fault current Ic
561
Man.Clos.Detect
OUT
Manual close signal detected
2720
>Enable ANSI#-2
SP
>Enable 50/67-(N)-2 (override 79 blk)
4601
>52-a
SP
>52-a contact (OPEN, if bkr is open)
2.1.6.4
Functions
2.1 General
SIPROTEC 4, 7SJ62/64, Manual
55
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...