Figure 2-5
Logic diagram for 50-2 high-set element for phases
If parameter
MANUAL CLOSE
is set to
50-2 instant.
or
50-3 instant.
and manual close detection is
used, a pickup causes instantaneous tripping, even if the element is blocked via binary input.
The same applies to 79 AR 50-2 inst. or 79 AR 50-3 inst.
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC 4, 7SJ62/64, Manual
59
C53000-G1140-C207-8, Edition 08.2016