Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
0
FLEXIBLE FUNC.
Flx
OFF
ON
Alarm Only
OFF
Flexible Function
0
OPERRAT. MODE
Flx
3-phase
1-phase
no reference
3-phase
Mode of Operation
0
BLK f out of r
Flx
YES
NO
YES
Block while Freq. is out of
range
0
MEAS. QUANTITY
Flx
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
dV/dt rising
dV/dt falling
Frequency
df/dt rising
df/dt falling
Binary Input
Please select
Selection of Measured
Quantity
0
MEAS. METHOD
Flx
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental
Selection of Measure-
ment Method
0
PICKUP WITH
Flx
Exceeding
Dropping below
Exceeding
Pickup with
0
CURRENT
Flx
Ia
Ib
Ic
In
In sensitive
In2
Ia
Current
F.2
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual
617
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...