Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
4009 46-TOC TIMEDIAL
46 Negative
Seq
0.50 .. 15.00 ; ∞
5.00
46-TOC Time Dial
4010 46-TOC TIMEDIAL
46 Negative
Seq
0.05 .. 3.20 sec; ∞
0.50 sec
46-TOC Time Dial
4011 46-TOC RESET
46 Negative
Seq
Instantaneous
Disk Emulation
Instantaneous
46-TOC Drop Out
4012A 46 T DROP-OUT
46 Negative
Seq
0.00 .. 60.00 sec
0.00 sec
46 Drop-Out Time Delay
4101 FCT 48
48/66 Motor-
prot
OFF
ON
OFF
48 Startup Time Supervi-
sion for Motors
4102 STARTUP CURRENT 48/66 Motor-
prot
1A
0.50 .. 16.00 A
5.00 A
Startup Current
5A
2.50 .. 80.00 A
25.00 A
4103 STARTUP TIME
48/66 Motor-
prot
1.0 .. 180.0 sec
10.0 sec
Startup Time
4104 LOCK ROTOR TIME 48/66 Motor-
prot
0.5 .. 180.0 sec; ∞
2.0 sec
Permissible Locked Rotor
Time
4105 STARTUP T WARM
48/66 Motor-
prot
0.5 .. 180.0 sec; ∞
10.0 sec
Startup Time for warm
motor
4106 TEMP.COLD
MOTOR
48/66 Motor-
prot
0 .. 80 %; ∞
25 %
Temperature limit for cold
motor
4201 FCT 49
49 Th.Overload
OFF
ON
Alarm Only
OFF
49 Thermal overload
protection
4202 49 K-FACTOR
49 Th.Overload
0.10 .. 4.00
1.10
49 K-Factor
4203 TIME CONSTANT
49 Th.Overload
1.0 .. 999.9 min
100.0 min
Time Constant
4204 49 Θ ALARM
49 Th.Overload
50 .. 100 %
90 %
49 Thermal Alarm Stage
4205 I ALARM
49 Th.Overload 1A
0.10 .. 4.00 A
1.00 A
Current Overload Alarm
Setpoint
5A
0.50 .. 20.00 A
5.00 A
4207A Kτ-FACTOR
49 Th.Overload
1.0 .. 10.0
1.0
Kt-FACTOR when motor
stops
4208A T EMERGENCY
49 Th.Overload
10 .. 15000 sec
100 sec
Emergency time
4209 49 TEMP. RISE I
49 Th.Overload
40 .. 200 °C
100 °C
49 Temperature rise at
rated sec. curr.
4210 49 TEMP. RISE I
49 Th.Overload
104 .. 392 °F
212 °F
49 Temperature rise at
rated sec. curr.
4211 TEMPSENSOR RTD
49 Th.Overload
1 .. 6
1
Temperature sensor
connected to RTD
4212 TEMPSENSOR RTD
49 Th.Overload
1 .. 12
1
Temperature sensor
connected to RTD
4301 FCT 66
48/66 Motor-
prot
OFF
ON
OFF
66 Startup Counter for
Motors
4302 IStart/IMOTnom
48/66 Motor-
prot
1.10 .. 10.00
4.90
I Start / I Motor nominal
4303 T START MAX
48/66 Motor-
prot
1 .. 320 sec
10 sec
Maximum Permissible
Starting Time
4304 T Equal
48/66 Motor-
prot
0.0 .. 320.0 min
1.0 min
Temperature Equalizaton
Time
4305 I MOTOR NOMINAL 48/66 Motor-
prot
1A
0.20 .. 1.20 A
1.00 A
Rated Motor Current
5A
1.00 .. 6.00 A
5.00 A
Functions, Settings, Information
F.2 Settings
632
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...