Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
7138 Internal SYNC
79M Auto Recl.
(Einstellmöglich-
keiten anwendung-
sabhängig)
none
Internal 25 synchronisa-
tion
7139 External SYNC
79M Auto Recl.
YES
NO
NO
External 25 synchronisa-
tion
7140 ZONE SEQ.COORD. 79M Auto Recl.
OFF
ON
OFF
ZSC - Zone sequence
coordination
7150 50-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-1
7151 50N-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-1
7152 50-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-2
7153 50N-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-2
7154 51
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
51
7155 51N
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
51N
7156 67-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67-1
7157 67N-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67N-1
7158 67-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67-2
7159 67N-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67N-2
7160 67 TOC
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67 TOC
7161 67N TOC
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67N TOC
7163 46
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
46
Functions, Settings, Information
F.2 Settings
644
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...