No.
Description
Function
Typ
e of
Info
rma
tion
Log Buffers
Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
1212
50Ns/67Ns is ACTIVE
(50Ns/67Ns ACT)
Sens. Gnd
Fault
OUT On
Of
f
*
*
LED
BO
15
1
11
2
1
Yes
1215
64 displacement voltage
pick up (64 Pickup)
Sens. Gnd
Fault
OUT *
On
Off
On
Off
*
LED
BO
15
1
11
5
2
Yes
1217
64 displacement voltage
element TRIP (64 TRIP)
Sens. Gnd
Fault
OUT *
On
On
Off
m LED
BO
15
1
11
7
2
Yes
1221
50Ns-2 Pickup (50Ns-2
Pickup)
Sens. Gnd
Fault
OUT *
On
Off
On
Off
*
LED
BO
15
1
12
1
2
Yes
1223
50Ns-2 TRIP (50Ns-2 TRIP) Sens. Gnd
Fault
OUT *
On
On
Off
m LED
BO
15
1
12
3
2
Yes
1224
50Ns-1 Pickup (50Ns-1
Pickup)
Sens. Gnd
Fault
OUT *
On
Off
On
Off
*
LED
BO
15
1
12
4
2
Yes
1226
50Ns-1 TRIP (50Ns-1 TRIP) Sens. Gnd
Fault
OUT *
On
On
Off
m LED
BO
15
1
12
6
2
Yes
1227
51Ns picked up (51Ns
Pickup)
Sens. Gnd
Fault
OUT *
On
Off
*
LED
BO
15
1
12
7
2
Yes
1229
51Ns TRIP (51Ns TRIP)
Sens. Gnd
Fault
OUT *
On
m LED
BO
15
1
12
9
2
Yes
1230
Sensitive ground fault
detection BLOCKED (Sens.
Gnd block)
Sens. Gnd
Fault
OUT On
Of
f
On
Off
*
LED
BO
15
1
13
0
1
Yes
1264
Corr. Resistive Earth
current (IEEa =)
Sens. Gnd
Fault
VI
ON
OF
F
1265
Corr. Reactive Earth
current (IEEr =)
Sens. Gnd
Fault
VI
ON
OF
F
1266
Earth current, absolute
Value (IEE =)
Sens. Gnd
Fault
VI
ON
OF
F
1267
Displacement Voltage
VGND, 3Vo (VGND, 3Vo)
Sens. Gnd
Fault
VI
ON
OF
F
1271
Sensitive Ground fault
pick up (Sens.Gnd Pickup)
Sens. Gnd
Fault
OUT On
Of
f
On
Off
*
LED
BO
15
1
17
1
1
Yes
1272
Sensitive Ground fault
picked up in Ph A (Sens.
Gnd Ph A)
Sens. Gnd
Fault
OUT On
Of
f
On
On
Off
*
LED
BO
16
0
48 1
Yes
1273
Sensitive Ground fault
picked up in Ph B (Sens.
Gnd Ph B)
Sens. Gnd
Fault
OUT On
Of
f
On
On
Off
*
LED
BO
16
0
49 1
Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ62/64, Manual
683
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...