Definite Time Directional High-set Elements 67-2, 67N-2, 67-3, 67N-3
For each element an individual pickup value
67-2 PICKUP
,
67-3 PICKUP
or
67N-2 PICKUP
,
67N-3
PICKUP
is set which can be measured as
Fundamental
or
True RMS
. Each phase current and the ground
current is compared with the common pickup value for each element
67-2 PICKUP
,
67-3 PICKUP
or
67N-2 PICKUP
,
67N-3 PICKUP
, and it is signaled when the value is exceeded provided that the fault direc-
tion is the same as the parameterized direction. After the associated delay times
67-2 DELAY
,
67-3 DELAY
or
67N-2 DELAY
,
67N-3 DELAY
have expired, the tripping commands are initiated which are equally avail-
able separately for each element. The dropout value is approximately 95% of the pickup value for currents >
0.3
Ι
Nom
.
Pickup can be stabilized by setting dropout times 1518
67 T DROP-OUT
or 1618
67N T DROP-OUT
. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the func-
tion does not drop out instantaneously. The trip delay times
50-2 DELAY
,
67-3 DELAY
or
50N-2 DELAY
,
67N-3 DELAY
continue during that time. After the dropout delay time has elapsed, the pickup is reported
OFF and the trip delay time is reset unless the threshold
50-2 PICKUP
,
67-3 PICKUP
or
50N-2 PICKUP
,
67N-3 PICKUP
has been exceeded again. If the threshold is exceeded again during the dropout delay time,
the time is canceled. The trip delay time
50-2 DELAY
,
67-3 DELAY
or
50N-2 DELAY
,
67N-3 DELAY
continues. If the threshold value is exceeded after this time has elapsed, the trip command is issued immedi-
ately. If the threshold value is not exceeded at this time, there is no reaction. If the threshold value is
exceeded again after expiry of the trip command delay time, while the dropout delay time is still running, trip-
ping is initiated immediately.
Each of these elements can be directional or non-directional (non-directional from V4.81 on).
These elements can be blocked by the automatic reclosing function (79 AR).
The following figure gives an example of the logic diagram for the high-set elements 67-2 of the phase
currents. The high-set element 67-3 is structured identically.
2.3.2
Functions
2.3 Directional Overcurrent Protection 67, 67N
SIPROTEC 4, 7SJ62/64, Manual
87
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...