Addr.
Parameter
C
Setting Options
Default Setting
_:2461:3
Supv. sum V:Threshold
0.300 V to 170.000 V
25.000 V
_:2461:6
Supv. sum V:Delay
failure indication
0.00 s to 100.00 s
5.00 s
VT miniatureCB
_:2641:101
VT minia-
tureCB:Response time
0.00 s to 0.03 s
0.00 s
Measuring Point V-1ph
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Rated primary
voltage
0.200 kV to 1200.000 kV
400.000 kV
_:2311:102
General:Rated secondary
voltage
80 V to 340 V
100 V
_:2311:108
General:Matching ratio
Vph / VN
0.10 to 9.99
1.73
_:2311:103
General:Tracking
•
inactive
•
active
inactive
_:2311:130
General:Measuring-point
ID
0 to 100
0
VT 1
_:3811:103
VT 1:Magnitude correc-
tion
0.010 to 10.000
1.000
_:3811:108
VT 1:Phase
•
V A
•
V B
•
V C
•
V AB
•
V BC
•
V CA
•
VN
•
Vx
•
VCB
•
VN broken-delta
_:3811:107
VT 1:Sequence number
device
1 to 2147483647
2147483647
VT miniatureCB
_:2641:101
VT minia-
tureCB:Response time
0.00 s to 0.03 s
0.00 s
Power-System Data
5.8 Settings
130
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...