i
i
NOTE
Due to the internal administration data, the complete flash memory size for the storing of recordings is not
available. The
Estimated record size
is user information in order to be able to estimate how many
recordings can be stored in the reserved flash memory. The actual size of the fault record depends on the
degree of compression and the number of stored events.
Parameter: Maximum Record Time
•
Default setting
(_:10081:111) Maximum record time
=
2 minutes
With the
Maximum record time
parameter, you set the maximum record time for an individual fault
recording. When the time configured expires, an ongoing fault recording is canceled. This parameter merely
limits the duration of the fault recording.
The maximum record duration includes the pre-trigger time.
Parameter: Pre-Trigger Time
•
Default setting
(_:10081:112) Pre-trigger time
=
5.0 s
With the
Pre-trigger time
parameter, you configure the pre-trigger time for an individual fault
recording. The pre-trigger time defines that time before a trigger event.
i
i
NOTE
The
Pre-trigger time
must be a maximum of 10 % of the
Post-trigger time
, as otherwise,
DIGSI 5 reports an inconsistency.
Parameter: Post-Trigger Time
•
Default setting
(_:10081:113) Post-trigger time
=
1 minute
With the
Post-trigger time
parameter, you configure the post-trigger time for an individual fault
recording. The post-trigger time defines that time after dropout of the trigger event.
Parameter: Manual Record Time
•
Default setting
(_:10081:116) Manual record time
=
1 minute
The parameter
Manual record time
determines the length of a recording if the fault recording is acti-
vated dynamically (edge-controlled) via a separately configured input signal
>Manual start
.
i
i
NOTE
The pre-trigger time, the post-trigger time, and the maximum record time have no effect in this case.
Parameter: Averaging Time
•
Default setting
(_:10081:140) Averaging time
=
1 period
With the
Averaging time
parameter, you determine the number of periods for which an average value will
be generated and stored in the memory.
The average value is always formed over the entire averaging time.
i
i
NOTE
The actual record time can differ from the parameterized record time since the actual record time is deter-
mined by the parameterized averaging time. The longer the averaging time, the larger the deviation can
be.
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual
245
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...