[dwTrendDef-220514-01, 1, en_US]
Figure 7-32
Operation of the Trend Recorder, Voltage Interruption
For the parameterization, specify a maximum memory capacity for the storage of recordings. The trend
recorder is organized as a ring buffer. When the memory is filled completely, the oldest data are overwritten
automatically.
Mode
The trend recorder operates only if the
Mode
is set to
on
.
Recording is interrupted if
Mode
is set to
off
during recording. Recording starts again if
Mode
is set again to
on
.
i
i
NOTE
In the mode
off
, the continuous recorder no longer records any measured values, but continues to record
device statuses (time jumps, modes
on
/
off
, as well as disconnection and recovery of the supply voltage).
PQDif recordings are still generated, even though the trend recorder is set to the mode
off
. It is recom-
mended to delete the recorder instance in case of long-term non-use.
Ring-Buffer Mode
With the trend recorder, data is stored on the flash memory in blocks. The new data of the last 10-minute
interval are available every 10 minutes. If, while recording of a record, the device determines that the free
space remaining on the recorder partition is too small, the oldest data block is erased automatically. During
this process, complete time segments in the specified grid are always lost.
Disconnection and Recovery of Supply Voltage
i
i
NOTE
If the supply voltage of the device is disconnected intentionally or by mistake, measuring gaps will appear
for the period of the disconnection. However, the recorded data remains stored and can be read after
recovery of the supply voltage.
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual
251
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...