[dwmintri-140213-01.tif, 1, en_US]
Figure 7-41
A New Trigger Reason (Min. Trigger) Extends the Fault Record
a
Trigger rising edge
b
Trigger falling edge
c
End of the retrigger blocking time (Max. trigger)
d
End of the retrigger blocking time (Min. trigger)
e
End of the post-trigger time
f
End of the maximum record time
t
Time line
If the identical trigger reason (for example,
Iph rms: C
) occurs again during the retrigger blocking time, the
retrigger blocking time restarts. The fault record is not extended. A new recording is only possible once a
trigger occurs outside the expired retrigger blocking time (see the following figure).
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual
259
C53000-G5040-C018-5, Edition 11.2017