Function Description Analog and Binary Triggers
Overview of Functions
The fast-scan and slow-scan recorders have analog and binary triggers.
Each analog trigger can be configured as primary, secondary or percentage value, relative to the rated value,
and switched into the mode ON, OFF or Test.
Fault records generated in test mode are marked with the Test (Test flag) identifier.
Many trigger combinations can be implemented using a CFC chart. To do this, various indications in CFC
blocks are processed into one CFC output signal that can then, for example, be routed to the External Start.
Analog Triggers
Table 7-5
Description of Analog Triggers
Analog Triggers
Description
Frequency trigger 1-phase
)
Frequency trigger 3-phase
)
Voltage trigger 1-phase
Voltage trigger 3-phase
Current trigger 1-phase
Current trigger 3-phase
Power trigger 1-phase
)
Power trigger 3-phase
)
In these function blocks level triggers (Min/Max) and gradient trigger (dM/dt) can be configured.
Binary Triggers
Table 7-6
Using Binary Triggers
Binary Triggers
Use
Manual start
Function key (via
>Manual start
)
Binary inputs
Via
>External start
GOOSE trigger
Via
>External start
CFC trigger
Via
>External start
Manual start and External start are each described in the chapters
and
7.3.3.2 External Trigger Start
Manual start and External start are 2 inputs on each recorder that can be used to start recording. The func-
tion is identical for both triggers. Manual Start is primarily used during commissioning and maintenance.
External Start is of universal use.
Function Description Analog Trigger
Structure of the Analog Trigger
There are 4 trigger functions available in the fault recorder:
•
Frequency trigger 1-phase (also see
)
•
Frequency trigger 3-phase (also see
)
•
Voltage trigger 1-phase (also see
)
•
Voltage trigger 3-phase (also see
)
7.3
7.3.1
7.3.2
7.3.2.1
Fault Recorder
7.3 Function Description Analog and Binary Triggers
262
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...