Parameter: Max. Trigger Active/Max. Trigger/Max. Trigger Hysteresis
•
Default setting
(_:9571:101) Max. trigger active
=
yes
•
Default setting
(_:9571:105) Max. trigger
=
120.000 V
•
Default setting
(_:9571:113) Max. trigger hysteresis
=
0.980 p.u.
With the
Max. trigger active
parameter, you activate the level trigger in order to monitor the voltage of
the fundamental component and prevent it from exceeding the set values.
Parameter Value
Description
yes
The voltage of the fundamental component is monitored for overvoltage.
no
The voltage of the fundamental component is not monitored for over-
voltage.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
Max. trigger
and can
be adjusted.
Parameter: Min. Trigger Active/Min. Trigger/Min. Trigger Hysteresis
•
Default setting
(_:9571:102) Min. trigger active
=
yes
•
Default setting
(_:9571:106) Min. trigger
=
80.000 V
•
Default setting
(_:9571:114) Min. trigger hysteresis
=
1.020 p.u.
With the
Min. trigger active
parameter, you activate the level trigger in order to monitor the voltage of
the fundamental component for dropping below the set values.
Parameter Value
Description
yes
The voltage of the fundamental component is monitored for undervoltage.
no
The voltage of the fundamental component is not monitored for under-
voltage.
The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter
Min. trigger
and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
•
Default setting
(_:9571:103) dM/dt rise active
=
no
•
Default setting
(_:9571:107) dM/dt rise (/Filter time)
=
20.000 V
•
Default setting
(_:9571:115) dM/dt rise hysteresis
=
0.980 p.u.
•
Default setting
(_:9571:112) Filter time
=
2 periods
With the
dM/dt rise active
parameter, you activate the gradient trigger in order to monitor the positive
gradients of the voltage of the fundamental component using the set filtering time (input in periods).
Parameter Value
Description
yes
The positive gradient of the voltage of the fundamental component is moni-
tored.
no
The positive gradient of the voltage of the fundamental component is not
monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt rise (/Filter
time)
and can be adjusted.
Parameter: dM/dt Drop Active - dM/dt Drop (/Filter Time) - dM/dt Drop Hysteresis - Filter Time
•
Default setting
(_:9571:104) dM/dt drop active
=
no
•
Default setting
(_:9571:108) dM/dt drop (/Filter time)
=
20.000 V
Fault Recorder
7.4 Trigger Functions 1-Phase
SIPROTEC 5, Fault Recorder, Manual
275
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...