Parameter Value
Description
yes
The RMS value of the voltage is monitored for undervoltage.
no
The RMS value of the voltage is not monitored for undervoltage.
If the
Min. trigger
does not operate phase-selectively, the set threshold value of the parameter
Min.
(Non-phs sel.)
applies to all phases.
If the
Min. trigger
operates phase-selectively, set the threshold values for the
Min. trigger
separately
for each phase. Then, the parameters
Min. phs A(AB)
,
Min. phs B(BC)
, and
Min. phs C(CA)
are
effective.
The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter
Min. (Non-phs sel.)
and can be adjusted.
Parameter: +dM/dt dM/dt/+dM/dt hysteresis
•
Default setting
(_:9601:103) +dM/dt active
=
no
•
Default setting
(_:9601:107) +dM/dt (Non-phs sel.)
=
20.000 V
•
Default setting
(_:9601:124) +dM/dt phs A(AB)
=
20.000 V
•
Default setting
(_:9601:125) +dM/dt phs B(BC)
=
20.000 V
•
Default setting
(_:9601:126) +dM/dt phs C(CA)
=
20.000 V
•
Default setting
(_:9601:115) +dM/dt hysteresis
=
0.980 p.u.
•
Default setting
(_:9601:112) Filter time
=
2 periods
With the
+dM/dt active
parameter, you activate the gradient trigger in order to monitor the positive gradi-
ents of the RMS value of the voltage using the set filtering time (input in periods).
Parameter Value
Description
yes
The positive gradient of the RMS value of the voltage is monitored.
no
The positive gradient of the RMS value of the voltage is not monitored.
If the gradient trigger does not operate phase-selectively, the set threshold value of the parameter
+dM/dt
(Non-phs sel.)
applies to all phases.
If the gradient trigger operates phase-selectively, set the threshold values for the gradient trigger separately
for each phase. Then, the parameters
+dM/dt phs A(AB)
,
+dM/dt phs B(BC)
, and
+dM/dt phs C(CA)
are effective.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
+dM/dt (Non-phs
sel.)
and can be adjusted.
Parameter: -dM/dt active/- dM/dt/-dM/dt hysteresis
•
Default setting
(_:9601:104) -dM/dt active
=
no
•
Default setting
(_:9601:108) -dM/dt (Non-phs sel.)
=
20.000 V
•
Default setting
(_:9601:127) -dM/dt phs A(AB)
=
20.000 V
•
Default setting
(_:9601:128) -dM/dt phs B(BC)
=
20.000 V
•
Default setting
(_:9601:129) -dM/dt phs C(CA)
=
20.000 V
•
Default setting
(_:9601:116) -dM/dt hysteresis
=
0.980 p.u.
•
Default setting
(_:9601:112) Filter time
=
2 periods
With the
-dM/dt active
parameter, you activate the gradient trigger in order to monitor the negative gradi-
ents of the RMS value of the voltage using the set filtering time (input in periods).
Parameter Value
Description
yes
The negative gradient of the RMS value of the voltage is monitored.
Fault Recorder
7.5 Trigger Functions 3-Phase
304
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...