Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
•
Default setting
(_:9871:103) dM/dt rise active
=
no
•
Default setting
(_:9871:107) dM/dt rise (/Filter time)
=
0.300 A
•
Default setting
(_:9871:115) dM/dt rise hysteresis
=
0.980 p.u.
•
Default setting
(_:9871:112) Filter time
=
2 periods
With the
dM/dt rise active
parameter, you activate the gradient trigger in order to monitor the positive
gradients of the current in the negative-sequence system using the set filtering time (input in periods).
Parameter Value
Description
yes
The positive gradient of the current in the negative-sequence system is
monitored.
no
The positive gradient of the current in the negative-sequence system is not
monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt rise (/Filter
time)
and can be adjusted.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:9751:1
Trig. I fund 1:Mode
•
off
•
on
•
test
off
_:9751:117
Trig. I fund 1:Phase-
selective
•
no
•
yes
no
_:9751:112
Trig. I fund 1:Filter time
2 cycles to 250 cycles
2 cycles
Max. trigger
_:9751:101
Trig. I fund 1:Max. active
•
no
•
yes
yes
_:9751:105
Trig. I fund 1:Max. (Non-
phs sel.)
1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9751:118
Trig. I fund 1:Max. phs A 1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9751:119
Trig. I fund 1:Max. phs B 1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
7.5.2.9
Fault Recorder
7.5 Trigger Functions 3-Phase
SIPROTEC 5, Fault Recorder, Manual
323
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...