Addr.
Parameter
C
Setting Options
Default Setting
_:9751:116
Trig. I fund 1:-dM/dt
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
General
_:9781:1
Trig. I RMS 1:Mode
•
off
•
on
•
test
off
_:9781:117
Trig. I RMS 1:Phase-
selective
•
no
•
yes
no
_:9781:112
Trig. I RMS 1:Filter time
2 cycles to 250 cycles
2 cycles
Max. trigger
_:9781:101
Trig. I RMS 1:Max. active
•
no
•
yes
yes
_:9781:105
Trig. I RMS 1:Max. (Non-
phs sel.)
1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9781:118
Trig. I RMS 1:Max. phs A 1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9781:119
Trig. I RMS 1:Max. phs B 1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9781:120
Trig. I RMS 1:Max. phs C 1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9781:113
Trig. I RMS 1:Max. hyste-
resis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
Min. trigger
_:9781:102
Trig. I RMS 1:Min. active
•
no
•
yes
yes
_:9781:106
Trig. I RMS 1:Min. (Non-
phs sel.)
1 A @ 100 Irated 0.030 A to 100.000 A
0.800 A
5 A @ 100 Irated 0.15 A to 500.00 A
4.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
0.800 A
5 A @ 50 Irated
0.15 A to 250.00 A
4.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.800 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
4.000 A
Fault Recorder
7.5 Trigger Functions 3-Phase
326
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...