Addr.
Parameter
C
Setting Options
Default Setting
_:9781:115
Trig. I RMS 1:+dM/dt
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
dM/dt drop (/Filter time)
_:9781:104
Trig. I RMS 1:-dM/dt
active
•
no
•
yes
no
_:9781:108
Trig. I RMS 1:-dM/dt
(Non-phs sel.)
1 A @ 100 Irated 0.030 A to 100.000 A
0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A
1.50 A
1 A @ 50 Irated
0.030 A to 50.000 A
0.300 A
5 A @ 50 Irated
0.15 A to 250.00 A
1.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.300 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
1.500 A
_:9781:127
Trig. I RMS 1:-dM/dt phs
A
1 A @ 100 Irated 0.030 A to 100.000 A
0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A
1.50 A
1 A @ 50 Irated
0.030 A to 50.000 A
0.300 A
5 A @ 50 Irated
0.15 A to 250.00 A
1.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.300 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
1.500 A
_:9781:128
Trig. I RMS 1:-dM/dt phs
B
1 A @ 100 Irated 0.030 A to 100.000 A
0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A
1.50 A
1 A @ 50 Irated
0.030 A to 50.000 A
0.300 A
5 A @ 50 Irated
0.15 A to 250.00 A
1.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.300 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
1.500 A
_:9781:129
Trig. I RMS 1:-dM/dt phs
C
1 A @ 100 Irated 0.030 A to 100.000 A
0.300 A
5 A @ 100 Irated 0.15 A to 500.00 A
1.50 A
1 A @ 50 Irated
0.030 A to 50.000 A
0.300 A
5 A @ 50 Irated
0.15 A to 250.00 A
1.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.300 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
1.500 A
_:9781:116
Trig. I RMS 1:-dM/dt
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
Trigger I0 1
_:9811:1
Trigger I0 1:Mode
•
off
•
on
•
test
off
_:9811:101
Trigger I0 1:Max. trigger
active
•
no
•
yes
yes
_:9811:105
Trigger I0 1:Max. trigger 1 A @ 100 Irated 0.030 A to 100.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 500.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 50.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 250.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:9811:113
Trigger I0 1:Max. trigger
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:9811:103
Trigger I0 1:dM/dt rise
active
•
no
•
yes
no
Fault Recorder
7.5 Trigger Functions 3-Phase
328
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...