Addr.
Parameter
C
Setting Options
Default Setting
_:9901:108
Trigger Psum 1:dM/dt
drop (/Filter time)
1 A @ 100 Irated 0.36 Wto 6000.00 W
34.64 W
5 A @ 100 Irated 1.80 W to 300000.00 W
173.21 W
_:9901:116
Trigger Psum 1:dM/dt
drop hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:9901:112
Trigger Psum 1:Filter
time
2cyclesto250 cycles
2 cycles
Trigger Qsum 1
_:9961:1
Trigger Qsum 1:Mode
•
off
•
on
•
test
off
_:9961:111
Trigger Qsum 1:Power
direction
•
negative
•
positive
positive
_:9961:101
Trigger Qsum 1:Max.
trigger active
•
no
•
yes
yes
_:9961:105
Trigger Qsum 1:Max.
trigger
1 A @ 100 Irated 0.36 var to 60000.00 var
207.85 var
5 A @ 100 Irated 1.80 var to 300000.00 var
1039.23 var
_:9961:113
Trigger Qsum 1:Max.
trigger hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:9961:102
Trigger Qsum 1:Min.
trigger active
•
no
•
yes
yes
_:9961:106
Trigger Qsum 1:Min.
trigger
1 A @ 100 Irated 0.36 var to 60000.00 var
138.56 var
5 A @ 100 Irated 1.80 var to 300000.00 var
692.82 var
_:9961:114
Trigger Qsum 1:Min.
trigger hysteresis
1.010 p.u. to 1.100 p.u.
1.020 p.u.
_:9961:103
Trigger Qsum 1:dM/dt
rise active
•
no
•
yes
no
_:9961:107
Trigger Qsum 1:dM/dt
rise (/Filter time)
1 A @ 100 Irated 0.36 var to 60000.00 var
34.64 var
5 A @ 100 Irated 1.80 var to 300000.00 var
173.21 var
_:9961:115
Trigger Qsum 1:dM/dt
rise hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:9961:104
Trigger Qsum 1:dM/dt
drop active
•
no
•
yes
no
_:9961:108
Trigger Qsum 1:dM/dt
drop (/Filter time)
1 A @ 100 Irated 0.36 var to 60000.00 var
34.64 var
5 A @ 100 Irated 1.80 var to 300000.00 var
173.21 var
_:9961:116
Trigger Qsum 1:dM/dt
drop hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:9961:112
Trigger Qsum 1:Filter
time
2cyclesto250 cycles
2 cycles
Trigger Ssum 1
_:10021:1
Trigger Ssum 1:Mode
•
off
•
on
•
test
off
_:10021:101
Trigger Ssum 1:Max.
trigger active
•
no
•
yes
yes
_:10021:105
Trigger Ssum 1:Max.
trigger
1 A @ 100 Irated 0.36 VA to 60000.00 VA
207.85 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA
1039.23 VA
_:10021:113
Trigger Ssum 1:Max.
trigger hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:10021:102
Trigger Ssum 1:Min.
trigger active
•
no
•
yes
yes
Fault Recorder
7.5 Trigger Functions 3-Phase
SIPROTEC 5, Fault Recorder, Manual
345
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...