High-Speed Relay with Semiconductor Acceleration (Type HS)
Switching capacity
On/Off: 1000 W/VA
Contact voltage
AC 200 V, DC 250 V
Permissible current per contact (continuous)
5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact
250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Make time, typical: 0.2 ms; maximum: 0.2 ms
Break time, typical: 9 ms; maximum: 9 ms
Rated data of the output contacts in accordance with
UL certification
B150
Q300
Power Relay (for Direct Control of Motor Switches)
Switching capacity for permanent and periodic operation
250 V/4.0 A
220 V/4.5 A
110 V/5.0 A
60 V/5.0 A
48 V/5.0 A
24 V/5.0 A
1000 W
1000 W
550 W
300 W
240 W
120 W
In order to prevent any damage, the external protec-
tion circuit must switch off the motor in case the rotor
is blocked.
Turn on switching power for 30 s, recovery time until switching on again is 15 minutes.
For short-term switching operations, an impulse/pause ratio of 3 % must be considered.
100 V/9.0 A
60 V/10.0 A
48 V/10.0 A
24 V/10.0 A
1000 W
600 W
480 W
240 W
Continuous and inching operation is not permitted.
In order to prevent any damage, the external protec-
tion circuit must switch off the motor in case the rotor
is blocked.
AC and DC contact voltage
250 V
Permissible continuous current per contact
5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s
Short-time current across closed contact
250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
≤ 16 ms
Rated data of the output contacts in accordance with
UL certification
DC 300 V, 4.5 A - 30 s ON, 15 min OFF
DC 250 V, 1 hp motor - 30 s ON, 15 min OFF
DC 110 V, 3/4 hp motor - 30 s ON, 15 min OFF
DC 60 V, 10 A, 1/2 hp motor - 30 s ON, 15 min OFF
DC 48 V, 10 A, 1/3 hp motor - 30 s ON, 15 min OFF
DC 24 V, 10 A, 1/6 hp motor - 30 s ON, 15 min OFF
Interference suppression capacitors across the
contacts
4.7 nF, ± 20 %, AC 250 V
The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at a time
thereby avoiding a power-supply short circuit.
Technical Data
11.1 General Device Data
SIPROTEC 5, Fault Recorder, Manual
431
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...