Supervision Functions
Voltage-Balance Supervision
Setting Values
Release threshold
0.300 V to 170.000 V
Increments of 0.001 V
Threshold min/max
0.58 to 0.95
Increments of 0.01
Delay failure indication
0.00 s to 100.00 s
Increments of 0.01 s
Dropout Ratio
Overvoltage dropout ratio
Approx. 0.97
Undervoltage dropout ratio
Approx. 1.05
Times
Tripping time
Approx. 500 ms
Dropout time
Approx. 500 ms
Voltage-Sum Supervision
Setting Values
Threshold
0.300 V to 170.000 V
Increments of 0.001 V
Delay failure indication
0.00 s to 100.00 s
Increments of 0.01 s
Dropout Ratio
Dropout ratio
Approx. 0.97
Times
Tripping time
Approx. 500 ms
Dropout time
Approx. 500 ms
Voltage Phase-Rotation Supervision
Setting Values
Tripping delay
0.00 s to 100.00 s
Increments of 0.01 s
Phase-rotation direction
A B C
A C B
Times
Tripping time
Approx. 500 ms
Dropout time
Approx. 500 ms
11.5
11.5.1
11.5.2
11.5.3
Technical Data
11.5 Supervision Functions
SIPROTEC 5, Fault Recorder, Manual
441
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...