OperatorBlocked using the values
TRUE
,
FALSE
The OperatorBlocked quality attribute indicates whether an object transferred via GOOSE message origi-
nates from a device that is in a
functional logoff
state. When the sending device is switched off,
the object is no longer being received and assumes the
invalid
state. However, since the Operator-
Blocked quality was previously identified on the receiver device, the object can be treated differently at
the receiving end (see chapter
3.3.2 Quality Processing/Affected by the User for Received GOOSE Values
At the receiving end, the object may be treated like a dropped signal.
Influencing Quality by the Operating Modes
In addition to the normal operation, the device also supports further operating modes that influence quality:
•
Test mode of the device
You can switch the entire device to test mode. In this case, all data objects generated in the device (state
values and measured values) receive the quality attribute Test =
TRUE
.
The CFC charts are also in test mode and all output data receive the quality attribute Test =
TRUE
.
•
Test mode for individual functions, stages, or function blocks
You can switch individual functions, stages, or function blocks into test mode. In this case, all data
objects generated by the function, stage, or function block (state values and measured values) receive
the quality attribute Test =
True
.
•
Functional logoff of the device
If you take the device out of operation and want to isolate it from the supply voltage, you can function-
ally log off the device ahead of time. Once you functionally log off the device, all data objects generated
in the device (state values and measured values) receive the quality attribute OperatorBlocked =
TRUE
.
This also applies to the output from CFC charts.
If objects are transferred via a GOOSE message, the receiver devices can assess the quality. The receiver
device detects a functional logoff of the transmitting device. After shutting down the sending device, the
receiver device identifies that the sending device has been logged off operationally and did not fail. Now
the receiving objects can automatically be set to defined states (see chapter
Affected by the User for Received GOOSE Values
•
Switching off individual functions, stages, or function blocks
You can switch off individual functions, stages, or function blocks. In this case, all data objects generated
by the function, stage, or function block (state values and measured values) receive the quality attribute
Validity =
invalid
.
Influencing the Quality through Hardware Supervision
Supervision functions monitor the device hardware (see chapter
8.4 Supervision of the Device Hardware
the supervision functions identify failures in the data acquisition of the device, all recorded data will receive
the quality attribute Validity =
invalid
.
Influencing the Quality by the User
You can influence the processing of data and their quality differently. In DIGSI 5, this is possible at the
following 3 locations:
•
In the Information routing editor for external signals of GOOSE connections
•
In the CFC chart
•
In the Information routing editor for binary input signals of device-internal functions
The following chapters describe in more detail the options regarding this influence as well as the automatic
quality processing.
If a GOOSE connection is the data source of a binary input signal of a device-internal function, you can influ-
ence processing of the quality at 2 locations: at the GOOSE connection and at the input signal of the function.
This is based on the following: A GOOSE date can be distributed within the receiving device to several func-
System Functions
3.3 Processing Quality Attributes
68
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...