[sc_LB_GOOSE_1, 1, en_US]
Figure 3-25
Advanced Quality Attributes for GOOSE Later Binding
With the following advanced quality attributes, you can filter the transmitted GOOSE indications and check
and set their quality. The values that have been adapted, if necessary, are forwarded to the receiver.
For the tests, you can select from the following setting options depending on the data type.
Table 3-5
Value Definitions
Setting Value
Description
Apply safe state value
The value configured in the Safe state is forwarded as valid to the appli-
cation as soon as communication disturbance occurs.
Keep value
The disturbed quality attribute is overwritten with
good
and the received
value is forwarded as valid to the application. If no value was received,
the output value is assumed being in safe state.
Keep last valid value
If an invalid quality attribute is received, the last valid value is forwarded
to the application. If no value has yet been received, the output value is
assumed being in safe state.
Set value to "false"
Applies only to Boolean communication objects. Every invalid quality
attribute causes the valid value
false
to be forwarded to the applica-
tion.
Set value to "true"
Applies only to Boolean communication objects. Every invalid quality
attribute causes the valid value
true
to be forwarded to the application.
These settings of the Advanced quality attributes apply to the advanced quality attributes listed below. The
selection can vary depending on the data type.
System Functions
3.3 Processing Quality Attributes
70
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...