Chatter test time
During this second test time, the number of times a signal changes its state is checked once again. The
time begins when the
chatter dead time
expires. If the number of status changes is within the
permissible limits, the signal is released. Otherwise, an additional dead time begins, unless the maximum
number of chatter checks has been reached.
Enter a number between 2 and 65535 in this field. The number entered corresponds to the time in
seconds. An entry is possible here only if the number of chatter checks does not equal 0.
As soon as chatter blocking is set, the corresponding signal is assigned the oscillatory quality, and a corre-
sponding indication is entered in the operational log.
The following image shows an example of the usage of chatter blocking on a single-point indication (type
SPS). The number of permitted status changes is set to 5. After 5 status changes occur, the signal is set to the
original state and it is given the quality oscillatory.
[dwflatsp-140212-01.tif, 1, en_US]
Figure 3-41
Signal Change During Chatter Blocking
System Functions
3.6 Other Functions
94
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...