[scmuio212, 1, en_US]
Figure 6-52
Parameters of the Measuring-Transducer Channels.
The fast measuring-transducer channels can be configured either as current or as voltage inputs. Apart from
this, their function corresponds to the basic function of the 20-mA-channels (see chapter
).
Application and Setting Notes
Parameter:
TD input-signal type
•
Default setting
(_:101) TD input-signal type
=
Current input
With the parameter
TD input-signal type
you determine whether the measuring-transducer input
channel works as a
Current input
or as a
Voltage input
.
Make sure that the selected channel has also been wired correctly (see Hardware manual, Input and Output
Module IO212).
Parameter:
Unit
•
Default setting
(_:103) Unit
=
A
With the parameter
Unit
, you set the physical unit of measurement of the measured values. The possible
setting values are listed in the settings table.
Parameter:
Measuring window
•
Default setting
(_:142) Measuring window
=
10 ms
With the parameter
Measuring window
, you set the measuring window that is used to determine the arith-
metic mean value from the sampled values. In case of slowly varying signals, Siemens recommends setting the
top value to 100 ms. With this value, a new, current measured value is provided every 100 ms for further
processing.
6.5.6.4
Function-Group Types
6.5 Function-Group Type Analog Units
190
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...