Figure 7-20
Routing of the Signals in the Information Routing
Application and Setting Notes – General Settings
The following figure shows the memory splitting of the different recorders and the general settings of the FG
Recorder.
[sc_RecorderGeneral, 1, en_US]
Figure 7-21
FG Recorder – General Settings
Parameter: Scaling COMTRADE
•
Recommended setting value
Scaling COMTRADE
=
Secondary values
With the
Scaling COMTRADE
parameter, you scale the fault-record data for the COMTRADE format. Possible
setting values are
Primary values
or
Secondary values
.
Memory Splitting
The maximum flash-memory capacity of the recorder is 15 GB.
Using the parameter
Flash-memory size
you can change the flash-memory capacity of each individual
recorder.
Several thousand recordings can be stored, depending on the flash-memory capacity.
7.2.4
Fault Recorder
7.2 Function-Group Type Recorder
234
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...