Application and Setting Notes
Settings of the Trend-Recorder Function
[scTrend-051014, 1, en_US]
Figure 7-33
Settings of the Trend Recorder
The procedure is described in chapter
7.1.2 Step 1: Creating a New Project and Adding a New Device
and in
the DIGSI Help.
Parameter: Flash-Memory Size
•
Recommended setting value
(_:10111:161) Flash-memory size
=
1000 MB
With the parameter
Flash-memory size
, you specify a maximum memory capacity of the trend recorder
on the mass storage.
If the flash memory becomes full while recording new fault records, the device automatically deletes the
oldest data in order to continue recording (ring buffer).
The record time is limited by the set flash-memory size and the number of events occurring.
i
i
NOTE
If you change the capacity of the recorder or delete a recorder instance, the flash memory of the device is
reorganized and all recordings of the device – not just those of the changed recorder – are automatically
and irrevocably deleted.
Before this, save your recordings by exporting them manually in DIGSI 5 or archiving them in SICAM PQS.
Then, delete your recordings in DIGSI 5 to avoid inconsistencies between new and old recordings.
You can find the description for routing the measurand in chapter
You can find the description on setting the tolerances (frequency and voltage) in the chapters
7.6.4.3 Application and Setting Notes
.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2731:1
General:Mode
•
off
•
on
on
Control
_:15361:161
Trend 1:Flash-memory
size
0.200 GB to 14.800 GB
1.000 GB
7.2.9.4
7.2.9.5
Fault Recorder
7.2 Function-Group Type Recorder
252
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...