Figure 7-45
dM/dt
dM
Change of the measurand
dt
Change of the filter time
Function Description Binary Trigger
Manual Trigger Start
The fast-scan recorder and the slow-scan recorder can be manually triggered.
They can trigger the start of the recording as follows:
•
Manually by the fault recorder (function key on the operation panel)
•
Via DIGSI 5
•
Via any IEC 61850 client (e.g., SICAM PQS with IEC 61850)
i
i
NOTE
The manual trigger is started by pressing the function keys routed to the
>Manual start
. In the applica-
tion templates, Function key 1 is the default for the fast-scan recorder and Function key 2 is the default
for the slow-scan recorder (see
).
The record time depends on the configured value
Manual record time
for the manual trigger start.
Manual Start of the Trigger with Information Routing
For the fast-scan recorder and the slow-scan recorder, you route the manual trigger start in the Information
routing in the matrix row >Manual start to the inputs that can be assigned binary signals.
[scmantrm-280113-01.tif, 1, en_US]
Figure 7-46
Routing the Manual Trigger Start
7.3.3
7.3.3.1
Fault Recorder
7.3 Function Description Analog and Binary Triggers
SIPROTEC 5, Fault Recorder, Manual
265
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...