Parameter: Release threshold
•
Recommended setting value
(_:101) Release threshold
=
0.5 A
for I
rated
= 1 A or
2.5 A
for I
rated
= 5 A
The
Release threshold
parameter is used to set the lower limit of the maximum phase current (I
max
).
Parameter: Delay failure indication
•
Recommended setting value
(_:6) Delay failure indication
=
5.00 s
Set the
Delay failure indication
parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv. balan. I
_:1
Supv. balan. I:Mode
•
off
•
on
•
test
off
_:101
Supv. balan. I:Release
threshold
1 A @ 100 Irated 0.030 A to 35.000 A
0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
2.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
2.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
2.500 A
_:102
Supv. balan. I:Threshold
min/max
0.10 to 0.95
0.50
_:6
Supv. balan. I:Delay
failure indication
0.00 s to 100.00 s
5.00 s
Information List
No.
Information
Data Class
(Type)
Type
Supv. balan. I
_:82
Supv. balan. I:>Block function
SPS
I
_:54
Supv. balan. I:Inactive
SPS
O
_:52
Supv. balan. I:Behavior
ENS
O
_:53
Supv. balan. I:Health
ENS
O
_:71
Supv. balan. I:Failure
SPS
O
Current-Sum Supervision
Overview of Functions
In healthy system operation, the sum of all currents at one measuring point must be approximately 0. The
Current-sum supervision function monitors the sum of all currents of one measuring point in the secondary
circuit. It detects connection errors during commissioning or short circuits and interruptions in the secondary
circuit.
For summation of the currents, the device requires the phase currents and the ground current of the current
transformer neutral point or of a separate ground-current transformer at this measuring point. Select the
following connection variant:
•
Current-transformer connections connected to 3 current transformers and the neutral point (see
8.3.6.5
8.3.6.6
8.3.7
8.3.7.1
Supervision Functions
8.3 Supervision of the Secondary System
386
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...