Shielding Concept
The measuring accuracy of the fault recorder can only be maintained if the voltage and current signals are
connected to the device using shielded lines (1).
Siemens recommends stopping the cable shield at a maximum of 10 cm before the device terminals (1) and
connecting the cable shields near the device with low impedance via the shield terminals (4) to ground poten-
tial (2).
[dwbackvi-130213-01.tif, 2, en_US]
Figure A-19
Shielding Concept
(1)
Shielded lines
(2)
To the main grounding busbar, cross-section at least 16 mm
2
(3)
Protective-conductor carrier rail
(4)
Shield terminal
(5)
Protective-conductor terminal of the device
•
Recommended control line for voltage signals: 4•2•0.75 mm
2
stranded shielded pair, for example,
LiYCY 4x2x0.75
•
Recommended control line for current signals: 4•2•2.5 mm
2
stranded shielded pair, for example,
LiYCY 4x2x2.5
i
i
NOTE
Make sure not to damage the cable shield!
A.7
Appendix
A.7 Shielding Concept
SIPROTEC 5, Fault Recorder, Manual
471
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...