Data Substitute Values
Depending on the data type, different data substitute values must be used.
Data Type
Possible Data Substitute Values
ACD, ACT
general
0 (False), 1 (True)
(The directional information is always manually updated with
unknown
.
PhsA, phsB, phsC, and neut are manually updated with the same
value just like how the general value is set.)
BAC, APC
mxVal
Floating-point range and range of values according to IEEE 754
(single precision)
BCR
actVal
–2
63
to 2
63
– 1
CMV
mag, ang
Floating-point range and range of values according to IEEE 754
(single precision)
DPC, DPS
stVal
0, 1, 2, 3 (intermediate-state, off, on, bad-state)
INC
stVal
–2 147 483 648 to 2 147 483 647
INS
stVal
–2 147 483 648 to 2 147 483 647
ISC, BSC
valWTr.posVal
–64 to 64
valWTr.transInd
0 (False), 1 (True)
SPC, SPS
stVal
0 (False), 1 (True)
MV
mag
Floating-point range and range of values according to IEEE 754
(single precision)
For controllable types, the following substitute values apply in addition to the settable state values or meas-
ured values:
ctlNum
=
0
stSeld
=
False
origin.orIdent =
Substituted by quality processing
origin.orCat
=
AUTOMATIC_BAY
Previous Quality Processing/Affected by the User for Received GOOSE Values
In the Information Routing editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type.
•
In the DIGSI 5 project tree, double-click Information Routing.
•
Select the desired signal in the External Signals group.
•
Open the Properties window and select the Processing Quality Attributes sheet.
System Functions
3.3 Processing Quality Attributes
72
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...