Other Functions
Indication Filtering and Chatter Blocking for Input Signals
Input signals can be filtered to suppress brief changes at the binary input. Chatter blocking can be used to
prevent continuously changing indications from forming a jam in the event list. In addition, an overload situa-
tion is avoided using chatter blocking. After an adjustable number of changes, the indication is blocked for a
certain period.
The settings for indication filtering can be found at the individual signals. The next figure shows the parame-
ters using the example of an input signal.
[sc7keson-260213-01.tif, 1, en_US]
Figure 3-39
Parameters of the Indication Filtering
The setting range for the
Software filtering time
parameter ranges from 0 ms to 86 400 000 ms (1
day) in ms increments. The Retrigger filter check box can be used to select whether the software filter should
be restarted by a change from 1 to 0 and back. When activated, the Indication timestamp before filtering
check box back dates the time stamp by the set software filtering time and the fixed hardware filtering time.
In this case, the time stamp corresponds to the actual status change of the signal.
3.6
3.6.1
System Functions
3.6 Other Functions
92
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...