![background image](http://html.mh-extra.com/html/siemens/siprotec-7sa511/siprotec-7sa511_instruction-manual_383123279.webp)
$SSHQGL[
6$
9
&*&
Annunciations 7SA511 for LSA (DIN 19244 and according IEC 60870-5-103)
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
FNo.
- Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
V
: Annunciation with Value
M
: Measurand
LSA No.- Number of annunciation for former LSA (DIN 19244)
according to IEC 60870-5-103:
CA
- Compatible Annunciation
GI
- Annunciation for General Interrogation
BT
- Binary Trace for fault recordings
Typ
- Function type (p: according to the configured "Function type")
Inf
- Information number
¿©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©©©©§©©©§©©©©©©©©©©©©©©©©¤
Ann.LSA
VDEW/ZVEI
FNo. Meaning
OpFtNo.CAGIBTTypInf
¨©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©©©ª©©ª©©ª©©ª©©©ª©©©
11>User defined annunciation 1
CG 24CAGIBT p 27
12>User defined annunciation 2
CG 25CAGIBT p 28
13>User defined annunciation 3
CG 26CAGIBT p 29
14>User defined annunciation 4
CG 27CAGIBT p 30
15>Testing via system-interface
135 53
16>Block. of monitoring dir. via sys.-int
135 54
51Device operative / healthy
CG 1 GI 135 81
52Any protection operative
CG
CAGI p 18
55Re-start of processor system
C 8CA p 4
56Initial start of processor system
C 14CA p 5
59Real time response to LSA
C 6
60LED Reset
C 13CA p 19
61Logging and measuring functions blockedCG
CAGI p 20
62Test mode
CG
CAGI p 21
63PC operation via system interface
CG
GI 135 83
95Parameters are being set
CG 11CAGI p 22
96Parameter set A is active
CG 40CAGI p 23
97Parameter set B is active
CG 41CAGI p 24
98Parameter set C is active
CG 42CAGI p 25
99Parameter set D is active
CG 43CAGI p 26
110Annunciations lost (buffer overflow)
C 9 135130
112Annunciations for LSA lost
C 10 135131
113Fault tag lost
BT135136
140General internal failure of device
CG
CAGI p 47
141Failure of internal 24 VDC power supplyCG 96 GI 135161
143Failure of internal 15 VDC power supplyCG 97 GI 135163
144Failure of internal 5 VDC power supply CG 98 GI 135164
145Failure of internal 0 VDC power supply CG 99 GI 135165
151Failure in I/O module 1
CG 100 GI 135166
152Failure in I/O module 2
CG 101 GI 135167
154Supervision trip circuit
CG
CAGI p 36
160Common alarm
CG
CAGI p 46
161Measured value supervision of currents CG
CAGI p 32
162Failure: Current summation supervision CG 104 GI 135182
163Failure: Current symmetry supervision CG 107 GI 135183
164Measured value supervision of voltages CG
CAGI p 33
165Failure: Voltage sum superv. (ph-e)
CG 105 GI 135184
166Failure: Voltage sum superv. (ph-ph)
CG 106 GI 135185
167Failure: Voltage symmetry supervision CG 108 GI 135186
168Failure: Measuring voltages absent
CG 109 GI 135187
169Fuse failure monitor operated (>10s)
CG 110 GI 135188
¥©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©©©¦©©¦©©¦©©¦©©©¦©©©¾