1200 DIST.PROT. GENERAL SETTINGS
1201 DIST.PROT.
Distance protection function
ON
[ ] on
OFF
[ ] off
1202 DIR. FD&T4
Direction for fault detection directional trip
FORWARDS
[ ] Forwards
REVERSE
[ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1203 T4
Delay T4 fault detection directional trip
min. 0.00
s
max. 32.00/Ñ
©©©©
1204 T5
Delay T5 fault detection non-directional trip
min. 0.00
s
max. 32.00/Ñ
©©©©
1205 MAN. CLOSE
Distance zone effective with manual close
Z1B DIRECTIONAL [ ] Z1B directional
Z1B NON DIRECT. [ ] Z1B non-directional
FD EFFECTIVE
[ ] Fault detection
Z1 EFFECTIVE
[ ] Z1 effective
1216 RAR -> Z1B
Distance zone Z1B effective before 1st RAR
YES
[ ] yes
NO
[ ] no
1217 DAR BLOCK
Effective zone if DAR is blocked
Z1; T1
[ ] Z1; T1
Z1; T1B
[ ] Z1; T1B
1218 DAR -> Z1L
Distance zone Z1L effective before DAR
YES
[ ] yes
NO
[ ] no
1221 BLK.AR Z1B
Autoreclosure is blocked for Z1B faults
NO
[ ] no
WITHIN
[ ] Within
OUTSIDE
[ ] Outside
1222 BLK.AR Z1L
Autoreclosure is blocked for Z1L faults
NO
[ ] no
WITHIN
[ ] Within
OUTSIDE
[ ] Outside
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1300 DIST.PROT. INDEPEND. ZONES
1301 R1
Zone 1: Resistance (phase-phase) R1
min. 0.05
Ï
max. 65.00
©©©©
1302 X1
Zone 1: Reactance (reach) X1
min. 0.05
Ï
max. 130.00
©©©©
1303 R1E
Zone 1: Resistance (phase-earth) R1E
min. 0.05
Ï
max. 130.00
©©©©