1400 DIST.PROT. CONTROLLED ZONES
1401 R1B
Zone 1B: Resistance (phase-phase) R1B
min. 0.05
Ï
max. 65.00
©©©©
1402 X1B
Zone 1B: Reactance (reach) X1B
min. 0.05
Ï
max. 130.00
©©©©
1403 R1BE
Zone 1B: Resistance (phase-earth) R1BE
min. 0.05
Ï
max. 130.00
©©©©
1404 DIREC. Z1B
Zone 1B: Direction
FORWARDS
[ ] Forwards
REVERSE
[ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1405 T1B 1PHASE
Zone 1B: Delay for single phase faults T1B 1PH
min. 0.00
s
max. 32.00/Ñ
©©©©
1406 T1B >1PHAS
Zone 1B: Delay for multi-phase faults T1B
min. 0.00
s
max. 32.00/Ñ
©©©©
1411 R1L
Zone 1L: Resistance (phase-phase) R1L
min. 0.05
Ï
max. 65.00
©©©©
1412 X1L
Zone 1L: Reactance (reach) X1L
min. 0.05
Ï
max. 130.00
©©©©
1413 R1LE
Zone 1L: Resistance (phase-earth) R1LE
min. 0.05
Ï
max. 130.00
©©©©
1414 DIREC. Z1L
Zone 1L: Direction
FORWARDS
[ ] Forwards
REVERSE
[ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1415 T1L
Zone 1L: Delay for all faults T1L
min. 0.00
s
max. 32.00/Ñ
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1500 DIST.PROT. FAULT DETEC.PROG
1501 PROG. U/I
Program for U/I fault detection
LE:Uphe/LL:Uphph [ ] LE:Uphe/LL:Uphph
LE:Uphph/LL:Uphp [ ] LE:Uphph/LL:Uphp
LE:Uphe/LL:Uphe [ ] LE:Uphe/LL:Uphe
LE:Uphe/LL:I>>
[ ] LE:Uphe/LL:I>>
1503 PROG. ZA
Program for impedance fault detection
LE:Zphe/LL:Zphph [ ] LE:Zphe/LL:Zphph
LE:Zphe/LL:I>>
[ ] LE:Zphe/LL:I>>