Functions
6-11
7SA522 Manual
C53000-G1176-C119-2
sidual) impedance factors is done in conjunction with the general protection data (refer
to Section 6.1.3).
Closing time of the
circuit breaker
The closing time of the circuit breaker
(address 239) is necessary if the
synchro-check function of the relay is used also for asynchronous switching. In this
case, the relay calculates the ideal closing instant such that the two voltages (bus bar
and feeder) are in synchronism at the instant when the breaker primary contacts close.
Trip/Close
Command Duration
Under address
the minimum trip command duration
is set.
This applies to all protection and control functions which may issue a trip command.
This also determines the length of the trip command pulse when a circuit breaker trip
test is initiated via the device. This setting can only be modified with DIGSI
®
4 under
“Additional Settings”.
Under address
the maximum close command duration
is set.
This applies to all close commands issued by the device. It also determines the length
of the close command pulse when a circuit breaker test cycle is issued via the device.
It must be set long enough to ensure that the circuit breaker has securely closed.
There is no risk in setting this time too long, as the close command will in any event
be terminated following a new trip command from a protection function. This setting
can only be modified with DIGSI
®
4 under “Additional Settings”.
Circuit Breaker
Test
With the 7SA522 it is possible to initiate from the front of the device or with DIGSI
®
4
an on load circuit breaker test consisting of a trip and close command. The duration of
the commands is determined by the command duration settings above. With address
the duration from the end of the trip command up to the start
of the close command for this test is determined. This setting should not be shorter
than 0.1 s.
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...