Functions
6-113
7SA522 Manual
C53000-G1176-C119-2
6.6
Earth Fault Protection Teleprotection Schemes
With the aid of the integrated comparison logic, the directional earth fault protection
according to Section 6.5 can be expanded to a directional comparison protection
scheme.
Teleprotection
Methods
One of the stages which must be directional and set
)RUZDUG
is used for the direc-
tional comparison. This stage can only trip if a fault is also seen in the forward direction
at the other line end. A release (unblock) signal or a block signal can be transmitted.
The following teleprotection schemes are differentiated:
Permissive (release) schemes:
•
Directional comparison,
•
Directional unblock scheme.
Blocking scheme:
•
Blocking of the directional stage.
A further stage may be set as a non directional back up stage.
Signal Transmis-
sion Channels
For the signal transmission, one channel in each direction is required. For example,
fibre optic connections or voice frequency modulated high frequency channels via pilot
cables, power line carrier or microwave radio links can be used for this purpose. If the
same transmission channel as for the transmission by the distance protection (section
6.4) is used, the signalling logic must also be the same!
The signal transmission schemes are also suited to three terminal lines (teed feeders).
In this case, signal transmission channels are required from each of the three ends to
the each of the others in both directions.
During disturbances in the receiver or on the transmission path, the teleprotection sup-
plement may be blocked via a binary input.
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...