Stub Protection
A further overcurrent stage is the stub protection. It can however also be used as a
normal additional definite time overcurrent stage, as it functions independent of the
other stages.
A stub fault is a short-circuit located between the current transformer set and the line
isolator. It is of particular importance with the 1
1
/
2
–circuit breaker arrangement (Figure
Figure 6-79 Stub fault at an 1
1
/
2
–circuit breaker arrangement
If a short circuit current
I
A
and/or
I
B
flows while the line isolator 1 is open, this implies
that a fault in the stub range between the current transformers
I
A
,
I
B
, and the line iso-
lator exists. The circuit breakers CBA and CBC which carry short-circuit current may
be tripped without delay.The two sets of current transformers are connected in parallel
such that the current sum
I
A
+
I
B
represents the current flowing towards the line iso-
lator.
The stub protection is an overcurrent protection which is only in service when the state
of the line isolator indicates the open condition via a binary input “
”.
The binary input must therefore be operated via an auxiliary contact of the isolator. In
the case of a closed line isolator, the stub protection is out of service. In Figure 6-80
shows the logic diagram.
If the stub protection stage is to be used as a normal definite time overcurrent stage,
the binary input “
”, should be left without allocation or routing (ma-
trix). The enable input “
”, however, has to be constantly activated
(either via a binary input or via integrated logic (CFC) functions which can be config-
ured by the user.
Busbar A
busbar B
fe
ed
er
1
fe
ede
r 2
stub fault
I
A
I
B
I
k
=
I
A
+
I
B
line isolator 1
line isolator 2
CBA
CBB
CBC
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...