Functions
6-178
7SA522 Manual
C53000-G1176-C119-2
"
" (F.No. 2783)
The automatic reclosure is blocked (e.g. circuit-breaker not ready). This information
indicates to the operational information system that in the event of an upcoming sys-
tem fault there will be a final trip, i.e. without reclosure. If the automatic reclosure is
already started, this information does not appear.
"
" (F.No.
)
The automatic reclosure is not ready for reclosure at the moment. In addition to the
"
" (F.No.
) mentioned above there are also obstructions during
the course of the reclose cycles such as "action time expired" or "last reclaim time run-
ning". This information is particularly helpful during testing because no protection test
cycle with reclosure may be initiated during this state.
"
" (F.No.
)
This information appears following starting of the automatic reclosure function, i.e.
with the first trip command that can start the automatic reclosure function. If this
reclosure was successful (or any in the case of more than one), this information
resets with the expiry of the last reclaim time. If no reclosure was successful or if
reclosure was blocked, it ends with the last — the final — trip command.
"
" (F.No.
)
Request for sync check measurement to an external device. This information appears
at the end of a dead time after a three-pole trip if a sync check request was set for the
corresponding cycle. Reclosure only takes place when the sync. check device has
granted release "
" (F.No.
).
">Sync.release" (F.No.
)
Release of reclosure by an external sync. check device if this was requested by the
output information "
" (F.No.
).
F.No.
Alarm
Comments
2701
>AR on
>AR: Switch on auto-reclose function
2702
>AR off
>AR: Switch off auto-reclose function
2703
>AR block
>AR: Block auto-reclose function
2711
>AR Start
>External start of internal Auto reclose
2712
>Trip L1 AR
>AR: External trip L1 for AR start
2713
>Trip L2 AR
>AR: External trip L2 for AR start
2714
>Trip L3 AR
>AR: External trip L3 for AR start
2715
>Trip 1pole AR
>AR: External 1pole trip for AR start
2716
>Trip 3pole AR
>AR: External 3pole trip for AR start
2727
>AR RemoteClose
>AR: Remote Close signal
2731
>Sync.release
>AR: Sync. release from ext. sync.-check
2737
>BLOCK 1pole AR
>AR: Block 1pole AR-cycle
2738
>BLOCK 3pole AR
>AR: Block 3pole AR-cycle
2739
>BLK 1phase AR
>AR: Block 1phase-fault AR-cycle
2740
>BLK 2phase AR
>AR: Block 2phase-fault AR-cycle
2741
>BLK 3phase AR
>AR: Block 3phase-fault AR-cycle
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...