Appendix
B-16
3515 SYNC-CHECK Synchronism
and
Voltage Check
YES
NO
YES
Live bus / live line and Sync before AR
3516 Usync>
U-line< Synchronism
and
Voltage Check
YES
NO
NO
Live bus / dead line check before AR
3517 Usync<
U-line> Synchronism
and
Voltage Check
YES
NO
NO
Dead bus / live line check before AR
3518 Usync<
U-line< Synchronism
and
Voltage Check
YES
NO
NO
Dead bus / dead line check before AR
3519 OVERRIDE
Synchronism
and
Voltage Check
YES
NO
NO
Override of any check before AR
3530
Op.mode with MC
Synchronism and
Voltage Check
with consideration of CB
closing time
without consideration of CB
closing time
without consideration of CB
closing time
Operating mode with Man.Cl
3531
MC maxVolt.Diff
Synchronism and
Voltage Check
1.0..40.0 V
2.0 V
Maximum voltage difference
3532
MC maxFreq.Diff
Synchronism and
Voltage Check
0.03..2.00 Hz
0.10 Hz
Maximum frequency difference
3533
MC maxAngleDiff
Synchronism and
Voltage Check
2..60
°
10
°
Maximum angle difference
3535
MC SYNCHR
Synchronism and
Voltage Check
YES
NO
YES
Live bus / live line and Sync before MC
3536
MC Usyn> Uline<
Synchronism and
Voltage Check
YES
NO
NO
Live bus / dead line check before
Man.Cl
3537
MC Usyn< Uline>
Synchronism and
Voltage Check
YES
NO
NO
Dead bus / live line check before
Man.Cl
3538
MC Usyn< Uline<
Synchronism and
Voltage Check
YES
NO
NO
Dead bus / dead line check before
Man.Cl
3539
MC O/RIDE
Synchronism and
Voltage Check
YES
NO
NO
Override of any check before Man.Cl
3701
Uph-e>(>)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode Uph-e overvoltage
prot.
3701
FCT Uphase-e
Voltage Protection
OFF
Alarm Only
ON
ON
Phase-Earth Overvoltage function is
3702
Uph-e>
Voltage Protection
1.0..170.0 V
85.0 V
Uph-e> Pickup
3703
T Uph-e>
Voltage Protection
0.00..30.00 sec
2.00 sec
T Uph-e> Time Delay
3704
Uph-e>>
Voltage Protection
1.0..170.0 V
100.0 V
Uph-e>> Pickup
3705
T Sen-Imp(Uphe)
Voltage Protection
0.05..0.50 sec
0.25 sec
Time of Carrier Send Impulse (Uph-e)
3721
3U0>(>) (or Ux)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode 3U0 (or Ux) overvolt-
age
3722
3U0>
Voltage Protection
1.0..220.0 V
30.0 V
3U0> Pickup (or Ux>)
3723
3U0 Reset Ratio
Voltage Protection
0.50..0.95
0.80
3U0 (or Ux) Reset ratio
3724
T 3U0
Voltage Protection
0.00..30.00 sec
2.00 sec
T (3U0 or Ux) Time Delay
3725
T Sen-Imp 3UO
Voltage Protection
0.05..0.50 sec
0.25 sec
Time of Carrier Send Impulse (3U0 or
Ux)
3802
START
Fault Locator
Pickup
TRIP
Pickup
Start fault locator with
3805
Paral.Line Comp
Fault Locator
NO
YES
NO
Mutual coupling parall.line compensa-
tion
3806
Load Compensat.
Fault Locator
NO
YES
NO
Load Compensation
3901
FCT BreakerFail
Breaker Failure
ON
OFF
ON
Breaker Failure Protection is
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...