Configuration
5-3
7SA6 Manual
C53000-G1176-C156-2
Figure 5-1
Device Configuration dialogue box in DIGSI
®
4 — example
Before closing the dialogue box, transfer the modified functional setting to the relay by
clicking on the item
DIGSI
→
Device
. The data is stored in the relay in a non-volatile
memory buffer.
The configured functional scope can be viewed at the front of the relay itself, but can-
not be modified there. The settings associated with the functional scope can be found
in the
MAIN MENU
under
→
Settings
→
Device Config
.
Special Cases
Most settings are self-explanatory. Special cases are described below.
Each device (depending on the version ordered) can feature one or two protection
data interfaces for communicating the protection signals. In address
145
you
determine if protection data interface
P. INTERFACE 1
is to be used. For a protected
object with two ends each device requires at least one protection data interface. For
more ends it must be guaranteed that all associated devices are connected with each
other either directly or via other devices. For more detail on this topic read Section 6.4,
Communication Topology.
If the setting group change-over function is used, the setting in address
103
Grp
Chge OPTION
must be set to
Enabled
. In this case, it is possible to apply up to four
different groups of function parameters (refer also to Subsection 6.1.2). During normal
operation, a convenient and fast switch-over between these setting groups is possible.
The setting
Disabled
implies that only one function parameter setting group can be
applied and used.
Address
110
Trip mode
is only applicable for devices that can trip single-pole or
three-pole. Set
1-/3pole
if single-pole tripping is also desired, i.e. if 1pole or
1-/3pole automatic reclosure is used. A prerequisite is that the device is provided with
the internal automatic reclosure function or that an external automatic reclosure is
used. Furthermore the circuit breaker is suited for single-pole control.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...