Configuration
5-38
7SA6 Manual
C53000-G1176-C156-2
The settings for the monitoring criteria of the chatter blocking feature are set only once
for all binary inputs; however, the status of the chatter suppression can be set individ-
ually for each binary input. See “Filtering/ Contact Chatter Suppression” in Subsection
5.2.3.
The following should be noted:
•
If there is contact chatter at a binary input and the input is blocked, the correspond-
ing indication will be displayed with “CCF” (example: “
>Door open CCF ON
”). Al-
so, the indication “
Contact chatter filter
” reports this condition. Both mes-
sages are shown in the operating buffer (event log).
•
Chattering of a single point indication is set as ON (coming) if the binary input is ac-
tivated by energization (configured High-active).
•
Chattering of a single point indication is set as OFF (going) if the binary input is de-
activated by energization (configured Low-active).
•
If this behaviour causes undesired results in individual situations, an interlocking
may be configured in CFC.
•
Chattering of a double point indication will be considered as an “intermediate” con-
dition.
Note:
Chatter blocking cannot be activated for any of the standard protective indications.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...