Functions
6-6
7SA6 Manual
C53000-G1176-C156-2
To acknowledge the message, click
OK
, and the original value reappears. A new entry
can be made or another setting value can be modified.
Primary or
Secondary Values
Setting values can be entered and displayed in primary terms or secondary terms, as
desired. DIGSI
®
4 automatically performs the conversions based on the settings en-
tered for the transformer data and conversion ratios.
To switch between primary values and secondary values:
G
Click on
Options
in the menu bar, as shown in Figure 6-7.
G
Click on the desired alternative.
Another method is available by using the buttons
on the toolbar.
Figure 6-7
Selection of primary or secondary value entry — example
Additional Settings
Those settings that are modified only in special cases are typically hidden. They may
be made visible by checking on
Display Additional Settings
.
Confirmation
Each entry may be confirmed by clicking
Apply
. Valid values are accepted automat-
ically when another field is selected.
The final acceptance of a modified setting takes place once the setting mode is exited
(see below “Exiting the Setting Mode”).
The dialogue box may be closed by clicking
OK
. Once closed, another function may
be selected for setting modification, or you can exit the setting mode.
Exiting the
Setting Mode
In order to transfer the modified setting values to the relay, the user should click on
DIGSI
→
Device
. The user will be prompted for Password No. 5. After entering the
password and confirming with
OK
, data is transferred to the relay where modifications
become effective.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...