Functions
6-26
7SA6 Manual
C53000-G1176-C156-2
1118
RE/RL(Z1B...Z5)
-0.33..7.00
1.00
Zero seq. comp.factor RE/RL for
Z1B...Z5
1119
XE/XL(Z1B...Z5)
-0.33..7.00
1.00
Zero seq. comp.factor XE/XL for
Z1B...Z5
1120
K0 (Z1)
0.000..4.000
1.000
Zero seq. comp. factor K0 for
zone Z1
1121
Angle K0(Z1)
-135.00..135.00
°
0.00
°
Zero seq. comp. angle for zone
Z1
1122
K0 (> Z1)
0.000..4.000
1.000
Zero seq.comp.factor K0,higher
zones >Z1
1123
AngleI K0(> Z1)
-135.00..135.00
°
0.00
°
Zero seq. comp. angle, higher
zones >Z1
1126
RM/RL ParalLine
0.00..8.00
0.00
Mutual Parallel Line comp. ratio
RM/RL
1127
XM/XL ParalLine
0.00..8.00
0.00
Mutual Parallel Line comp. ratio
XM/XL
1128
RATIO Par. Comp
50..95 %
85 %
Neutral current RATIO Parallel
Line Comp
1130A
PoleOpenCurrent
0.05..1.00 A
0.10 A
Pole Open Current Threshold
1131A
PoleOpenVoltage
2..70 V
30 V
Pole Open Voltage Threshold
1132A
SI Time all Cl.
0.01..30.00 sec
0.05 sec
Seal-in Time after ALL closures
1134
Line Closure
Manual Close BI only
Current OR Voltage or
Manual close BI
CBaux OR Current or
Manual close BI
Current flow or Manual close
BI
Manual Close BI
only
Recognition of Line Closures
with
1135
Reset Trip CMD
with Pole Open Current
Threshold only
with CBaux AND Pole Open
Current
with Pole Open
Current Threshold
only
RESET of Trip Command
1140A
I-CTsat. Thres.
0.2..50.0 A;
∞
20.0 A
CT Saturation Threshold
1150A
SI Time Man.Cl
0.01..30.00 sec
0.30 sec
Seal-in Time after MANUAL clo-
sures
1151
MAN. CLOSE
with Synchronism-check
without Synchronism-check
NO
without Synchro-
nism-check
Manual CLOSE COMMAND
generation
1155
3pole coupling
with Pickup
with Trip
with Trip
3 pole coupling
1156A
Trip2phFlt
3pole
1pole, leading phase
1pole, lagging phase
3pole
Trip type with 2phase faults
Addr.
Setting Title
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...