Functions
6-37
7SA6 Manual
C53000-G1176-C156-2
settings which determine the geometry of the current/voltage characteristic. The an-
gle-dependent area which is shaded dark grey within the short-circuit angle area can
either have an effect in forward direction (in direction of line) or in both directions (set-
table).
Figure 6-20
U/I/
ϕ
characteristic
Loop pick-up will drop off if the signal falls below 95 % of the respective current value
or exceeds 105 % of the respective voltage value. A hysteresis of 5° applies to phase-
angle measuring.
Pickup Modes
As the U/I/
ϕ
fault detection represents an extension of the U/I fault detection according
to Section 6.2.2.2 the same program options apply. Tables 6-3 to 6-6 also apply for
single–phase pick-up.
6.2.2.4
Applying the Function Parameter Settings
Pickup Mode
Depending on the ordered version, the 7SA6 distance protection has a series of pick-
up modes from which the one matching the respective network conditions best can be
selected (also see order data in the Appendix).
If the device does not have an explicit pick-up function or, if you set
DIS ANR
=
Im-
pedance
(address
114
) for pick-up type when configuring the protection functions
(Section 5.1), all settings dealt with in this section are irrelevant and cannot be select-
ed.
Available pick-up modes are described in Section 6.2.2.1 and 6.2.2.2 in detail. If the
device has several alternative pick-up modes, one option has been selected when
configuring in address
114
(see Section 5.1). Below, parameters are given and dis-
cussed for all pick-up modes. With the following settings, only those parameters will
appear that apply for the selected pick-up mode.
With the U/I(/
ϕ
) pick-up mode you have the option to determine the voltage measuring
and, if applicable, the phase-angle measuring for phase–to–earth measuring units,
1
2
3
10
20
30
40
50
60
U
V
I
I
N
U(I
ϕ
>)
U(I>>)
U(I>)
I
ph>
I
ϕ
>
I
ph>>
Short-circuit angle
area
ϕ
>
Load area
Short-circuit
area at
ϕ
<
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...