Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
1601
PROGAM U/I
Ph-E: Uphe/ Ph-Ph: Uphph
Ph-E: Uphph/Ph-Ph: Uphph
Ph-E: Uphe/Ph-Ph: Uphe
Ph-E: Uphe/Ph-Ph: I>>
Ph-E: Uphe/ Ph-Ph:
Uphph
Pickup program U/I
1602
DELAY FORW. PU
0.00..30.00 sec;
∞
1.20 sec
Trip delay for Forward-PICKUP
1603
DEL. NON-DIR PU
0.00..30.00 sec;
∞
1.20 sec
Trip delay for non-directional
PICKUP
1630A
1ph FAULTS
phase-earth
phase to phase only
phase-earth
1ph-pickup loop selection (PU
w/o earth)
1610
Iph>>
0.25..10.00 A
1.80 A
Iph>> Pickup (overcurrent)
1611
Iph>
0.10..4.00 A
0.20 A
Iph> Pickup (minimum current)
1612
Uph-e (I>>)
20..70 V
48 V
Undervoltage (ph-e) at Iph>>
1613
Uph-e (I>)
20..70 V
48 V
Undervoltage (ph-e) at Iph>
1614
Uph-ph (I>>)
40..130 V
80 V
Undervoltage (ph-ph) at Iph>>
1615
Uph-ph (I>)
40..130 V
80 V
Undervoltage (ph-ph) at Iph>
1616
Iphi>
0.10..8.00 A
0.50 A
Iphi> Pickup (minimum current
at phi>)
1617
Uph-e (Iphi>)
20..70 V
48 V
Undervoltage (ph-e) at Iphi>
1618
Uph-ph (Iphi>)
40..130 V
80 V
Undervoltage (ph-ph) at Iphi>
1619A
EFFECT
ϕ
forward and reverse
Forward
forward and reverse
Effective direction of phi-pickup
1620
ϕ
>
30..60
°
50
°
PHI> pickup (lower setpoint)
1621
ϕ
<
90..120
°
110
°
PHI< pickup (upper setpoint)
F.No.
Alarm
Comments
3781
Dis.TimeOut Tfw
DistanceTime Out Forward PICKUP
3782
Dis.TimeOut Tnd
DistanceTime Out Reverse/Non-dir. PICKUP
3695
Dis Pickup
ϕ
L1
Dist.: Phi phase L1 Pickup
3696
Dis Pickup
ϕ
L2
Dist.: Phi phase L2 Pickup
3697
Dis Pickup
ϕ
L3
Dist.: Phi phase L3 Pickup
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...